WEBWAYONE LTD, Unit 11 Kingfisher Court
Hambridge Road, Newbury, Berkshire. RG14 5SJ
00 44 1635 231 514 support@webwayone.co.uk
GE Aritech ATS series alarm panel connections and configuration using the
WebWay Dial Capture Module (DCM)
GE Aritech ATS 2000/3000/4000 /4500
To install the Aritech ATS for full remote management you will require the Dial Capture Module (DCM).
Connect the WebWay PSTN panel interface A and B or the A and B terminals on the WebWay DCM to the PSTN A and
B terminals on the ATS panel.
Connect the WebWay PWR + and - to any relevant Power and Ground terminals.
Aritech ATS series panel configuration
Select advanced service menu
Got to menu 9
Ensure PBX is blank
Ensure MSN is blank
Select Dial tone detection <UK>
Select DTMF tone dialling <YES>
Select Enable PSTN line fault monitor <NO>
Select Monitor Service tones <NO>
Select Use 3 digit SIA extensions <YES>
Select ISDN point to point <NO>
Select 200 baud reverse area open/close <NO>
Select X25 TEI value <2>
Select Audio listen in time <180>
Select Audio listen in frame time <30>
Select Report mains fault <YES>
Select Report line fault <YES>
Select Enable GSM line fault monitor <NO>
Select the central station to program <Central station 1>
Select the reporting format <X-SIA Large> (Option 7)
Enter the first phone number <01234 567890> (any valid phone number is acceptable)
Enter the system account number <______> (Site ID/Account Number)
Select BELL modem tones for SIA <YES>
Enter the Area account number <______> (Site ID/Account Number)
Select Dual reporting <NO>
Select Listen in <NO>
Select Disable reporting of inhibits <NO>